Practical examples Chapter 7.
7. Practical examples
Direct Ethernet VCOM to a Mitsubishi PLC
For this example, we want to reach a Mitsubishi PLC placed behind an eWON500.
eWON configuration
The eWON-LAN IP address was configured to 10.0.120.50 by eBuddy.
On the eWON, as the Mitsubishi PLC uses a RS-422 serial link, you will configure the
eWON serial dipswitch in RS-485/RS-422 mode:
The VCOM port configuration will be the following:
eVCOM (Standard serial communications) Page 15/29
10.0.120.1
10.0.120.50
Configuration → System Setup → General → Net Services → VCOM