1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE OF I/O
MODULE
(5) It is recommended to install fuses to external terminals per point to prevent the
external device and module from being burned in case of load short in the QY22 or
QY68A.
Operations of the following fuses have been checked and ensured by Mitsubishi.
Module model QY22*
1
QY68A*
2
Fuse model 216 02.5 216 002 216 3.15 312 003
Rated current 2.5A 2A 3.15A 3A
Manufacturer Littelfuse, Inc
*1: Fuses that conform to Sheet 1 of IEC60127 are recommended.
*2: Fast blow fuses whose rated current is 3A are recommended.
(6) Connecting the transistor output modules in parallel may result in a failure of the
output elements.
If connecting the transistor output modules in parallel, use diodes for the circuit as
shown below.
OUT1
Load
OUT2
COM
Load
OUT1
OUT2
COM
OUT1
Load
OUT2
COM
Load
OUT1
OUT2
COM
Sink type Source type