Vista de pagina 58
2 - 26 2 - 26
MELSEC-Q
2 INPUT MODULE SPECIFICATIONS
2.20 QX80H DC High-speed Input Module (Negative Common Type)
DC high-speed input module (Negative Common Type) Type
Specifications
QX80H Appearance
Number of input points 16 points
Isolation method Photocoupler
Rated input voltage 24VDC (+20/-15%, ripple ratio within 5%)
Rated input current Approx. 6mA
Input derating Refer to the derating chart.
ON voltage/ON current 13V or higer/3mA or higher
OFF voltage/OFF current 8V or lower/1.6mA or lower
Input impedance Approx. 3.9k
SW1 (noise
filter)
1
OFF ON
Set value 2 Invalid 0.1 0.2 0.4 0.6 1
TYP. 0ms 3 0.04ms 0.10ms 0.25ms 0.50ms 0.95ms
OFF to ON
MAX. -
3 0.05ms 0.15ms 0.30ms 0.60ms 1.00ms
TYP. 0ms 3 0.04ms 0.10ms 0.25ms 0.50ms 0.95ms
Response
time
ON to OFF
MAX. -
3 0.05ms 0.15ms 0.30ms 0.60ms 1.00ms
Function
setting
SW2
4 OFF: Interrupt, ON: High-speed input
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m (6557.38ft.))
Insulation resistance 10M or more by insulation resistance tester
Noise immunity 5
By noise simulator of 500Vp-p noise voltage, 1
s noise width
and 25 to 60Hz noise frequency
Protection of degree IP2X
Common terminal
arrangement
8 points/common (common terminal: TB9,TB18)
Number of I/O points
16 (I/O allocation is set as a 16-points high-speed input module or interrupt
module)
4
Interrupt processing condition Set by Switch setting in GX Developer 4 6
Operation indicator ON indication (LED)
External connections 18-point terminal block (M3 6 screws)
Applicable wire size 0.3 to 0.75mm
2
core (2.8mm (0.11in.)OD max.)
Applicable crimping terminal R1.25-3 (sleeved solderless terminals cannot be used.)
5VDC internal current
consumption
80mA (TYP. all points ON)
Weight 0.16kg
1: If turning on the switch 1, the noise filter takes effect.
The off-status noise filter disables I/O response time setting.
After switching on or off the switch 1, reset the power supply of the CPU module.
2: Set an input response time in
"
I/O response time
"
combo box of PLC parameter in GX Developer. (Default: 0.2ms)
The response time in SW6D5C-GPPW or later can be changed.
For the setting details, refer to Section 1.3.1.
3: The actual response time is 5 s delay when turning on, 10 s delay when turning off, because the hardware response time is added.
For the details of the CPU overhead time, refer to manuals for the CPU module used (Function Explanation, Program Fundamentals)...
4: The module function can be changed according to the switch 2 status.
ON : High-speed input
OFF : Interrupt
If changing the switch 2 setting while the CPU module is in RUN, an error (error code:2100) occurs.
5: Indicates the noise immunity when the noise filter takes effect (the switch is turned on).
6: For the setting method, refer to Section 1.3.3.
Vista de pagina 58