Chapter2 Connection to a PLC
2-122
4.4.2 SLC 500 (Half Duplex)
Item Setting
Communication Interface RS-232C
Baud Rate (bps) (*1)(*2) 1200, 2400, 4800, 9600, 19200
Data Bits (*2) 8 (fixed)
Parity (*1)(*2) None or Even
Stop Bits
(*1)(*2) 1
Driver (*1) DF1 Half-Duplex Slave (*4)
Duplicate Detect (*1) Disabled (*4)
Error Detect (*1) BCC (*4)
Control Line (*1) No handshaking (*4)
Node Address (*1)(*2)(*3) 0 to 254 (decimal)
(*1) Set using RSLogix500 (set Chan0 to System of Controller-Channel Configuration).
(*2) The setting for this item must match the setting on the HG Series unit.
(*3) Set the MICRO/I Node Address using the Node Address (HG) setting in Project Setting
of WindO/I-NV2.
(*4) Be certain to set as indicated.