Mitsubishi RS232/485/LAN Serial Communication Control Manual Pagina 290

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 349
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 289
Chapter2 Connection to a PLC
2-290
Word Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input Points (Word) XW V 40400 - 40477 R
(octal)
Output Points (Word) YW V 40500 - 40577 R/W
(octal)
Control Relays (Word) CW V 40600 - 40777 R/W
(octal)
Stages (Word) SW V 41000 - 41077 R/W
(octal)
Remote In (Word) GXW V 40000 - 40177 R/W
(octal)
Remote Out (Word) GYW V 40200 - 40377 R/W
(octal)
Special Relays (Word) SPW V 41200 - 41237 R
(octal)
Timer Values TV V 0 - 377 R/W
(octal)
Counter Values CV V 1000 - 1377 R/W
(octal)
Data Registers D V 1400 - 7377 R/W
(octal)
System Parameters1 SR1 V 700 - 777 R
(octal)
System Parameters2 SR2 V 7400 - 7777 R
(octal)
Ext Registers ER V 10000 - 37777 R/W
(octal)
We confirm only D4-440 address range. Depending on the type of PLC that you will be using,
the there are limits to the areas that can be used within the device ranges given above. Refer
to the PLC manual for details.
When selecting Bit Write, operation depends on the project settings which has an option to
turn off all other bits in the byte or leave all other bits without change. Check or uncheck the
check box for "Bit Write operation will write to a byte." (Byte refers to 8 bits.)
Check: When executing Bit Write, all other bits in the byte are turned off. Uncheck:
When executing Bit Write, all other bits are not changed. During Bit Write operation, the
MICRO/I reads the byte data including the designated bit from the PLC, performs logical
AND or OR operation with the designated bit, and writes the result into the PLC, therefore
all other bits in the byte are not changed.
Vista de pagina 289
1 2 ... 285 286 287 288 289 290 291 292 293 294 295 ... 348 349

Comentarios a estos manuales

Sin comentarios