Mitsubishi RS232/485/LAN Serial Communication Control Manual Pagina 134

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 349
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 133
Chapter2 Connection to a PLC
2-134
Word Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input WI
I
0 - 301 R 10 (*1)
Output WO
O
0 - 301 R 10 (*1)
Bit WB
B
3000 - 3255,
10000 - 255255
R/W 10 (*2)
Timer
(accumulated value)
TA
T
4000 - 4255,
10000 - 255255
R 10 (*2)
Counter
(accumulated value)
CA
C
5000 - 5255,
10000 - 255255
R 10 (*2)
Timer (preset value) TP
T
4000 - 4255,
10000 - 255255
R/W 10 (*2)
Counter
(preset value)
CP
C
5000 - 5255,
10000 - 255255
R/W 10 (*2)
Integer (*3) N
N
7000 - 7255,
10000 - 255255
R/W 10 (*2)
ASCII A
A
10000 - 255255 R/W 10 (*2)
(*3) Allocate the System Area above the file number 7 integer file. It will not operate with
file number 10 and above. You must construct an area above the SLC 500 data table
file that corresponds to the System Area Address set by WindO/I-NV2.
(*1) Address selection rule is as follows.
Standard device address format of WindO/I-NV2
WI
301
SLC 500 Address --- I 30.1
WindO/I-NV2 Address ---WI 301
1 di
g
its Word Number
2 di
g
its Slot Number
Allen-Bradley device address format
WI
30.1
1 di
g
its Word Number
2 di
g
its Slot Number
Vista de pagina 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 348 349

Comentarios a estos manuales

Sin comentarios