4 Allen-Bradley PLCs
2-145
Chap.2
(*3) Address selection rule is as follows.
Standard device address format of WindO/I-NV2
WB
255255
Example
MicroLogix1200 Address --- B
123:255
WindO/I-NV2 Address --- WB
123255
3 di
g
its Element number
3 di
g
its File number
Allen-Bradley device address format
WB
255
:
255
3 di
g
its Element number
3 di
g
its File number
(*4)
Address selection rule is as follows.
WindO/I-NV2 uses 32 bit device as the divided 2 word device.
Therefore, the last one digit shows that the device is upper word or lower word.
Standard device address format of WindO/I-NV2
F
2552551
MicroLogix1200 Address --- F
123:255
WindO/I-NV2 Address --- F
1232550 or F1232551
3 di
g
its Element number
3 di
g
its File number
1 digits 0: Lower word 1: Upper word
Allen-Bradley device address format
F
255
:
255
_
3di
g
its Element number
3di
g
its File number
1 digits 0: Lower word 1: Upper word
- WO,WI,WB are same devices as O,I,B. They are used as word devices.
- Floating Point (F) and Long Word (L) are 32-bit devices. When you write to these devices,
please be sure to write a high word and low word simultaneously. If you write only high
word or
only low word, 0 will be written into the other word.